Generators: Sizing, Fuel and Safe Operation

Power  12 min read

Almost every off-grid property needs a generator. It charges the batteries through long cloudy spells, runs heavy loads such as welders and well pumps that a modest inverter cannot carry, and keeps the property going when part of the power system fails. A generator is also the most dangerous piece of equipment many households own. Carbon monoxide from generators kills people every year, fuel stored badly causes fires, and a generator connected to house wiring without the right switch can electrocute a line worker or a family member. This guide covers generator types, sizing in watts and volt-amperes, fuel choice and storage limits, run time and fuel arithmetic, cold weather and altitude, safe placement, connecting to building wiring, maintenance and seasonal storage.

What the generator is for

Decide what the generator must do before choosing one. On an off-grid property it usually has one or more of these jobs:

  • Battery charging: the generator feeds the inverter-charger, which charges the bank and passes power to the house at the same time. Our solar sizing guide shows how to match the generator to the charger's input.
  • Direct heavy loads: power tools, welders, a deep-well pump or a construction site, run straight from the generator's outlets.
  • Backup for the whole system: carrying essential loads if the inverter, controller or battery fails, through a transfer switch.
  • Primary power: on a seasonal camp with no solar, the generator runs whenever power is needed and the property has little or no battery storage.

A generator used mainly for battery charging runs for a few hours at a time at a steady load, which suits most engines well. A generator used as primary power runs many hours at light and changing loads, which uses far more fuel per kilowatt-hour delivered.

Generator types

TypeDescriptionSuits
Inverter generatorEngine drives an alternator whose output is converted electronically to clean 60 Hz AC; engine speed follows the loadBattery charging, electronics, quiet operation, lighter loads
Conventional open-frame portableEngine runs at a fixed speed to hold 60 Hz; heavier and louderTools and construction, larger loads per dollar
Dual-fuel portableRuns on gasoline or propane, selected by a switch or valveProperties with propane already on site
Permanently installed standbyFixed unit on a pad, usually propane, natural gas or diesel, often with automatic startYear-round homes with large loads and long generator hours
PTO generatorDriven by a tractor's power take-off shaftFarms with a suitable tractor

Inverter generators vary engine speed with load, so they use less fuel and make less noise at light load. That makes them the usual choice for charging and for cabins close to neighbours. Conventional generators generally cost less per watt of output.

Automatic start

Many inverter-chargers can start a generator automatically when the battery falls to a set voltage or state of charge, if the generator has an electric start and a compatible remote start connection. This protects the battery at an unattended property, but it also means the generator will start with nobody present. Place it, fuel it and maintain it as if it will run alone, because it will.

Sizing a generator

Running and starting watts

Generators are sold with two figures. Running (rated) watts is what the generator can deliver continuously. Starting (surge or maximum) watts is what it can deliver for a few seconds while a motor starts. Some manufacturers rate in volt-amperes instead: Honda's EU2200i manual gives a rated output of 1.8 kVA for continuous operation and a maximum output of 2.2 kVA for short periods only, and warns that sustained overloads can damage the generator.

Continuous loading

The Ontario Ministry of Agriculture, Food and Rural Affairs (OMAFRA) advises running a generator at no more than 80% of its capacity for continuous operation. Size so that the steady load sits at or below that figure.

Worked example: sizing for a workshop and pump

A generator must run a table saw (1,800 W running), a shop vacuum (1,000 W) and lights (100 W) together, and the well pump (1,000 W running) may cycle on at any time.

Running load: 1,800 + 1,000 + 100 + 1,000 = 3,900 W.

Continuous rating needed at 80% loading: 3,900 ÷ 0.80 = 4,875 W.

Starting check: if the pump's motor starts while the other loads run, the generator's starting rating must cover the 2,900 W already running plus the pump's starting draw, taken from the pump maker's data or measured with a meter that captures inrush current.

A generator with about 5,000 W running output and a starting rating that covers the pump surge fits. Alternatively, run the saw and vacuum only when the pressure tank is full, and a smaller generator will do.

Watts and volt-amperes

Motors and some electronic loads draw more volt-amperes than watts, as our load audit guide explains. If a generator is rated in kVA, compare it with the loads' volt-amperes, not only their watts. A battery charger with a poor power factor can load a small generator more heavily than its watt rating suggests.

120 V and 240 V

Small inverter generators usually supply 120 V only. A 240 V well pump or an inverter-charger with a 240 V input needs a generator with a 240 V output. On a 120/240 V generator, balance 120 V loads between the two halves so that neither side is overloaded while the other sits idle.

Fuel choice

FuelAdvantagesDrawbacks
GasolineWidely available; most portable generators run on itDegrades in storage; strict indoor storage limits; fire risk when refuelling
PropaneDoes not go stale; stored in sealed cylinders or tanks; often already on site for cooking and heatLower power output than gasoline in the same generator; vaporizes poorly in extreme cold
DieselEngines built for long hours; fuel is less volatile than gasolineHigher purchase cost; fuel needs winter grade or treatment in cold weather

Propane output

Dual-fuel generators produce less running power on propane than on gasoline. One Champion dual-fuel inverter model is rated at 1,850 W running on gasoline and 1,665 W running on propane, with 2,500 W starting on either. That is a 10% reduction in running output on propane: (1,850 − 1,665) ÷ 1,850 = 0.10. Size a dual-fuel generator by its propane rating if propane will be its usual fuel.

Propane in cold weather

Propane leaves the cylinder as vapour, and liquid propane boils at about −42 °C (−44 °F). The colder the cylinder and the faster the vapour is drawn off, the lower the pressure, and a small cylinder feeding a large generator in deep cold may not keep up. Use the largest practical tank in winter, keep it out of snow and wind, and never heat a cylinder with a flame or electric heater.

Gasoline shelf life

Honda's EU2200i manual warns that gasoline can degrade in as little as 30 days, faster in warm storage. Its storage guidance is:

  • under 1 month: no preparation needed;
  • 1 to 12 months: fill with fresh gasoline treated with a stabilizer, and for the longer end of the range also drain the carburetor float bowl;
  • 1 year or more: drain the fuel tank and carburetor, change the oil, and add a little oil to the cylinder.

The same manual calls for regular unleaded gasoline of 86 pump octane or higher, with ethanol blends up to E10 permitted.

Fuel storage limits

Fire codes limit how much fuel may be kept in and around a home. British Columbia's Fire Code, which follows the National Fire Code of Canada, sets these limits. Gasoline is a Class I flammable liquid.

LocationAll flammable and combustible liquidsOf which Class I (gasoline)
Inside a dwelling unit30 L (7.9 US gal)10 L (2.6 US gal)
Attached garage or shed50 L (13.2 US gal)30 L (7.9 US gal)
  • Use containers built to an approved standard, such as CSA B376 portable containers for gasoline and other petroleum fuels, or ULC/ORD-C30 safety containers. A container that meets none of the listed standards may hold no more than 1 L of Class I liquid.
  • Containers must be labelled as flammable, to be kept away from heat, sparks and open flames, and kept closed when not in use.
  • Never store fuel in or beside exits or the routes to them.
  • Fuel in an engine's own tank is not counted toward these limits, but a generator with fuel in it is still a fire hazard in a living space.

Larger quantities belong in a detached, ventilated fuel shed well away from the house, or in a properly installed outdoor tank. Check your province's or state's fire code and your insurer's conditions before storing more than the household limits.

Run time and fuel arithmetic

Manufacturers state run time per tank, usually at 25% or 50% load. Use it to plan fuel for a cloudy week or a building project.

Worked example: fuel for a cloudy week

The Champion dual-fuel model above lists 11.5 hours of run time on its 1.05 US gal (4.0 L) gasoline tank and 25 hours on a 20 lb (9.1 kg) propane cylinder. The manufacturer's sheet does not state the load for these figures, so treat them as light-load best cases.

Gasoline use: 4.0 L ÷ 11.5 h = 0.35 L per hour.

Propane use: 9.1 kg ÷ 25 h = 0.36 kg per hour.

A cabin expects to run the generator 3 hours a day for 7 cloudy days: 3 × 7 = 21 hours.

  • Gasoline: 21 × 0.35 = 7.4 L. That fits in one approved 10 L container, which is also the indoor limit for Class I liquid, so keep it in a detached shed instead.
  • Propane: 21 × 0.36 = 7.6 kg, which is less than one 20 lb cylinder.

Add a margin of at least 50% for heavier loads and cold-weather starts, and measure your own consumption by noting fuel added against hours run.

Fuel per kilowatt-hour

Divide fuel used by energy delivered to compare generators and loading. Track both with an hour meter and the inverter-charger's log. A generator charging a battery at a steady, moderate load delivers far more kilowatt-hours per litre than the same generator idling under a light load all evening.

Cold weather and altitude

Cold starting

  • Use the oil viscosity the manual specifies for the temperature range. Honda's general recommendation for the EU2200i is SAE 10W-30, with other grades by temperature from a chart in the manual.
  • Keep the battery of an electric-start generator charged; cold reduces cranking power.
  • Shelter the generator from drifting snow without enclosing it. A shelter must stay open enough that exhaust cannot collect and that the engine has the cooling air the manual specifies.
  • Let the engine warm up briefly before applying full load.

Altitude

Engines lose power as air thins. Honda's manual states that above 1,500 m (5,000 ft) a dealer should modify the carburetor, and that even then power falls by about 3.5% per 300 m (1,000 ft). A modified carburetor must be returned to standard if the generator is used below 1,500 m, or the engine can overheat.

Worked example: altitude derate

A ranch cabin sits at 1,800 m (5,900 ft). Taking Honda's figure of 3.5% per 300 m: 1,800 ÷ 300 = 6, and 6 × 3.5% = 21%. A generator rated 3,000 W at sea level can be expected to deliver about 3,000 × (1 − 0.21) = 2,370 W, before any 80% continuous-loading allowance: 2,370 × 0.80 = 1,896 W.

Carbon monoxide and placement

The US Consumer Product Safety Commission (CPSC) reports that more than 80 people die each year in the United States from carbon monoxide poisoning caused by portable generators. Carbon monoxide cannot be seen or smelled and can kill within minutes.

  • Run a portable generator only outdoors. The CPSC advises at least 6 m (20 ft) from the house, with the exhaust pointed away from the home and other buildings.
  • Keep it away from windows, doors and vents, even when they are closed. Never run it in a house, garage, basement, crawl space, shed or porch, even with doors open.
  • Install CO alarms with battery power or battery backup on every level and outside sleeping areas, and test them monthly.
  • When buying, look for a model that shuts off automatically if CO builds up around it.

Early symptoms of CO poisoning include headache, dizziness, weakness, nausea, vomiting, sleepiness and confusion. If an alarm sounds or anyone has symptoms, get everyone outside at once and call 911.

Generators installed in buildings

Permanently installed generators inside a building need engineered ventilation and exhaust, and are covered by fuel, electrical and building rules. OMAFRA's guidance for farm generators calls for at least 500 cm² (0.5 sq ft) of combined air inlet and outlet opening per kilowatt of generator capacity, and exhaust pipes at least 150 mm (6 in) from combustible materials. Treat these as minimums and follow the manufacturer's installation instructions and local codes.

Connecting to building wiring

A generator can power loads in three ways: through cords plugged into its outlets, through an inverter-charger's AC input, or into the building's wiring through a transfer device.

Cords

Use grounded three-prong extension cords rated for the load, laid flat rather than coiled. Keep cord runs short, out of water and away from doorways where they can be pinched.

Transfer switches

Never plug a generator into a wall outlet or wire it into a panel without a transfer device. Honda's manual warns that connections to building wiring must be made by a qualified electrician with an isolation switch that separates generator power from any other source, because backfeed can injure utility workers and damage the generator. Hydro-Québec directs that permanent generator systems in Quebec be installed by a member of the Corporation des maîtres électriciens du Québec, with a compliant transfer switch.

On a property with no utility connection, a transfer device is still needed wherever the generator and an inverter could both supply the same wiring. Most inverter-chargers contain their own automatic transfer switch, which is why the generator connects to the inverter's AC input, not to the house panel.

Grounding and the neutral bond

Honda notes that on the EU2200i the frame ground connects to the receptacle ground terminals and is not tied to the neutral. Other generators bond neutral to frame internally. How your generator is built affects how it must be connected to an inverter-charger or transfer switch, because the neutral may be bonded to ground at only one point in a system. Give the generator's manual to the electrician who wires it.

Maintenance and storage

Routine checks

  • Check the engine oil before every use, and change it at the intervals in the manual, including any earlier first change on a new engine.
  • Check the air cleaner before every use, and clean it more often in dusty conditions.
  • Check, gap and replace the spark plug at the manual's intervals; the EU2200i specifies a gap of 0.6 to 0.7 mm.
  • Clean the spark arrester every 100 hours on the EU2200i, or as your manual states. A spark arrester matters on forested properties.
  • Fit an hour meter if the generator lacks one, and log hours, oil changes and fuel.

Exercising a standby generator

OMAFRA advises exercising a standby generator every 90 days under at least 50% load for 30 minutes, with 5 minutes at rated speed and no load, and a 5-minute cool-down before shutdown. Keep a year of test logs for reference and insurance.

Seasonal storage

Follow the fuel steps above for the storage period. Honda's procedure for long storage adds about 5 cc of clean oil to the cylinder through the spark plug hole, cranks the engine a few turns, and then pulls the starter slowly until resistance is felt. Store the generator level, away from flames and sparks, and under a breathable cover once the engine has cooled.

Key points

  • Decide whether the generator is for charging, heavy loads, backup or primary power, and choose the type to suit.
  • Size from running and starting watts, or volt-amperes, and keep continuous load at or below 80% of rated output.
  • Propane does not go stale, but it gave 10% less running output in one dual-fuel model; gasoline can degrade in 30 days without a stabilizer.
  • Under BC's Fire Code, keep no more than 10 L of gasoline in a dwelling and 30 L in an attached garage or shed, in CSA B376 or ULC/ORD-C30 containers.
  • Expect about 3.5% less power per 300 m above 1,500 m, even with a high-altitude carburetor.
  • Run portable generators outdoors at least 6 m (20 ft) from the house, install CO alarms, and refuel only a cooled engine.
  • Connect to building wiring only through a transfer device installed by a qualified electrician with the required permit.

This guide is general information. Codes, permits and safety requirements vary by province, state and municipality. Check local rules and use a qualified professional for electrical, gas, chimney and septic work where required.

The Comprehensive Off-Grid Manual

Every off-grid system in one manual, with worked examples, checklists and northern-climate detail.

Power

Off-Grid Batteries: LiFePO4 vs Lead-Acid

LiFePO4 vs lead-acid for off-grid power: usable capacity, cycle life, cold-weather charging, bank sizing, wiring, ventilation and lifetime cost.

13 min read
Power

The Electrical Load Audit and Efficiency

Measure every load with meters and battery monitors, find duty cycles and standby waste, plan peak demand, audit by season, and price efficiency upgrades.

13 min read