Inverters, Charge Controllers and System Monitoring

Power  13 min read

The inverter, the charge controllers and the battery monitor decide how well an off-grid power system uses the energy it collects. Choosing them well and setting them correctly protects the battery, cuts wasted power and gives early warning of problems. This guide explains how to read inverter specifications, what idle consumption costs, how to set an inverter-charger for a generator, how to program charge stages and temperature compensation, how a shunt battery monitor works, when AC coupling suits, and what to monitor day to day. It builds on our solar sizing guide, which covers basic controller and inverter selection.

What each part does

In a typical DC-coupled off-grid system, the MPPT charge controller converts array power to battery voltage and decides how much current the battery receives. The inverter converts battery power to 120 V or 120/240 V AC. When a generator runs, the inverter-charger passes its power to the loads and uses the surplus to charge the battery. A battery monitor on the battery's negative cable measures every amp in and out.

Each charging source runs its own charge program. If two controllers, an inverter-charger and a wind or hydro controller all charge the same battery, they must all be set to the same voltages. A controller set higher than the others will keep pushing current after the others have dropped to float.

Reading an inverter specification sheet

Inverter datasheets list many figures. These are the ones that decide whether a unit suits a cabin or home. The table compares two common 48 V inverter-chargers from their published datasheets.

SpecificationVictron MultiPlus-II 48/3000 (120 V)Schneider Conext XW Pro 6848
Continuous output at 25 °C (77 °F)2,400 W6,800 W
Continuous output at 40 °C (104 °F)2,200 W6,000 W
Surge or peak output5,500 W peak12,000 W for 60 seconds
Maximum efficiency95%95.1%
No-load or search-mode consumption11 W on, 7 W in AES mode, 2 W in search modeUnder 8 W in search mode
Maximum battery charge current35 A140 A
Transfer switch rating50 A60 A, typical transfer 8 ms
Output120 V120/240 V split phase
Safety listings shownCSA C22.2 No. 107.1, UL 1741CSA 107.1, UL 1741

Continuous rating and temperature

Output ratings fall as the inverter gets warmer. The MultiPlus-II above delivers 2,400 W at 25 °C, 2,200 W at 40 °C and 1,700 W at 65 °C. An inverter in a hot, unventilated closet or a sun-heated shed will not deliver its headline rating. Size the continuous rating for the warmest conditions the unit will see, and leave the ventilation clearances given in the manual.

VA and watts

The 48/3000 is a 3,000 VA model, but its continuous output at 25 °C is 2,400 W. Motors draw current out of step with voltage, so they load an inverter by more VA than the watts they use. Check loads against both ratings.

Surge rating and duration

A surge figure means little without its duration. One datasheet above gives a peak with no duration; the other gives 12,000 W for 60 seconds. A well pump or compressor needs high current while its motor comes up to speed. If the largest motor is close to the surge figure, ask the manufacturer how long the inverter holds that output.

Efficiency

Peak efficiency applies only near the best part of the load range; at light loads the fixed internal consumption lowers it. A weighted figure, such as the California Energy Commission (CEC) rating of 93.0% for the XW Pro, is a better guide to everyday performance.

Certification

In Canada, inverters and chargers for buildings are certified to CSA C22.2 No. 107.1, the standard for power conversion equipment. In the United States, look for a UL 1741 listing. UL 458 covers inverters for vehicles and boats, so check the label and ask your inspection authority whether a unit is accepted for a building.

Idle consumption and search mode

An inverter uses power whenever it is on, even with nothing plugged in. On a small system, idle draw can be one of the largest loads.

Worked example: what idle draw costs each day

The Victron MultiPlus-II 24/3000 lists 13 W with no load, 9 W in its AES mode and 3 W in search mode.

  • Left on all day: 13 W × 24 h = 312 Wh per day, or 312 × 365 = about 114 kWh per year.
  • AES mode all day: 9 W × 24 h = 216 Wh per day.
  • Search mode for the 18 hours a day with no loads, and fully on for 6 hours: (3 W × 18 h) + (13 W × 6 h) = 54 + 78 = 132 Wh per day.

Search mode saves 312 − 132 = 180 Wh per day in this example. On a short winter day, when a small array may produce only one or two kilowatt-hours, that saving is significant.

How search mode works

In search mode the inverter stops producing a steady AC output and sends short test pulses to see whether anything is drawing power. When a load above the set threshold appears, the inverter switches fully on. When the load disappears, it returns to searching.

  • Small loads such as phone chargers, clocks, smoke alarm interconnects and electronics on standby may not be large enough to wake the inverter. They will not work, or will cycle on and off.
  • Some loads draw just enough to keep the inverter on permanently, which defeats the saving. A plug-in energy meter shows which devices do this.
  • Do not use search mode if anything must have uninterrupted AC power, such as a freezer controller, a well pump pressure switch with an electronic control, an internet terminal or medical equipment.

Switching the inverter off when no AC loads are needed, such as overnight in a seasonal cabin, is the simplest saving of all.

Setting up an inverter-charger

Transfer switch

When generator power within the set voltage and frequency limits reaches the AC input, the internal transfer switch connects the loads to it. The XW Pro datasheet gives a typical transfer time of 8 ms. The transfer switch rating, 50 A or 60 A in the units above, limits how much current can pass through to the loads.

Input current limit

The most important setting for generator use is the AC input current limit. The inverter-charger reduces its charging current so that loads plus charging never exceed this limit. Set it below the generator's rated continuous output, not its starting surge.

Worked example: setting the input limit for a generator

A 120 V generator has a rated continuous output of 2,500 W. Its continuous current is 2,500 ÷ 120 = 20.8 A. The owner sets the input current limit to 16 A, which allows 16 × 120 = 1,920 W and keeps the generator at about 77% of its rating.

With 700 W of house loads running, the charger can draw 1,920 − 700 = 1,220 W. On a 24 V battery charging at 28 V, and with about 90% charger efficiency, that gives 1,220 × 0.90 ÷ 28 = about 39 A of charge current.

If the loads rise to 1,800 W, the charger drops to 1,920 − 1,800 = 120 W, and the generator stays within its limit.

Many inverter-chargers can also add battery power to the generator's output when loads briefly exceed the input limit. Victron calls this PowerAssist. This lets a small generator start a large motor, provided the battery has charge to spare.

Charger current

Set the inverter-charger's maximum charge current to what the battery maker allows. The MultiPlus-II 48/3000 can supply up to 35 A at 48 V; the 24/3000 version up to 70 A at 24 V. On a small battery, a large charger can exceed the battery's charge-rate limit.

Programming charge stages

Charge controllers and inverter-chargers run a multi-stage charge program. Names vary between makers.

  • Bulk. The charger delivers as much current as is available until battery voltage reaches the absorption setting.
  • Absorption. The charger holds the absorption voltage while current tapers off as the battery fills.
  • Float. The charger drops to a lower voltage that keeps a lead-acid battery full without overcharging. Many lithium batteries need no float, or a low float only.
  • Equalization. A periodic controlled overcharge for flooded lead-acid batteries only. Victron ships its MPPT controllers with equalization disabled and does not allow it on lithium presets.

Use the battery manufacturer's voltages. Factory defaults are a starting point only: the default absorption and float on Victron's SmartSolar MPPT 150/60 to 250/70 range, for example, are 28.8 V and 27.6 V on 24 V systems, which are not correct for every battery.

Ending absorption: time and tail current

Two methods decide when absorption ends.

  • Time. Absorption lasts a set time, or a time based on how deeply the battery was discharged. Victron's adaptive mode measures the battery voltage each morning before charging and chooses a fraction of the maximum absorption time, as in the table below.
  • Tail current. Absorption ends when charge current falls below a set level for one minute, which shows the battery is nearly full. Battery makers often give this as a percentage of capacity.
Morning battery voltage (24 V system)Share of maximum absorption timeAbsorption time with a 6-hour maximum
Below 23.8 VAll6 hours
23.8–24.2 VTwo-thirds4 hours
24.2–25.2 VOne-third2 hours
Above 25.2 VOne-sixth1 hour

Fixed absorption times can overcharge lead-acid batteries that are only lightly discharged each day. Victron's manual warns of this when adaptive absorption is turned off.

Temperature compensation and cold cut-off

Lead-acid batteries need higher charge voltages when cold and lower ones when warm. Without compensation, a cold battery is undercharged and a hot one overcharged.

Victron's default compensation is −16 mV per °C for 12 V systems, −32 mV per °C for 24 V and −64 mV per °C for 48 V, referenced to 25 °C (77 °F).

Worked example: absorption voltage on a cold battery

A 24 V flooded battery has an absorption setting of 28.8 V at 25 °C, with compensation of −32 mV per °C.

Battery at 5 °C (41 °F): 25 − 5 = 20 °C below reference. 20 × 0.032 = 0.64 V. Absorption becomes 28.8 + 0.64 = 29.44 V.

Battery at 35 °C (95 °F): 10 °C above reference. 10 × 0.032 = 0.32 V. Absorption becomes 28.8 − 0.32 = 28.48 V.

Check that the inverter's high-voltage shutdown and any DC loads can tolerate the cold-weather figure.

Compensation only works if the charger knows the battery's temperature. A controller that uses its own internal sensor measures the air around the controller, not the battery. Fit a battery temperature sensor to the battery itself, or share a battery temperature reading over the equipment's data network. For lithium batteries, follow the battery maker's instructions on compensation.

LiFePO4 batteries must not be charged below freezing. Most have a BMS that blocks cold charging, but chargers can also stop charging at low temperature. Victron's low-temperature cut-off is off by default, defaults to 5 °C (41 °F) when enabled, and works only when the controller receives a battery temperature reading. Our battery guide covers cold-weather charging limits in detail.

Shunt battery monitors

A battery's voltage is a poor fuel gauge, especially for LiFePO4. A shunt-based battery monitor counts amp-hours in and out, much like a fuel meter, and reports state of charge (SOC) as a percentage.

How it works

A shunt is a precise low-resistance bar on the battery's negative cable. Current flowing through it produces a small voltage across it, which the monitor converts into amps. All current must pass through the shunt: only the battery negative connects on the battery side, and every load, charger and inverter negative connects on the other side. Anything wired directly to the battery negative is invisible to the monitor.

Settings that matter

Victron SmartShunt defaults are shown as an example.

SettingDefaultPurpose
Battery capacity200 AhMust match your bank's rated capacity.
Charged voltage14.0 V, 28.0 V or 56.0 VVoltage the battery must reach to be counted as full. Victron suggests 13.9 V, 27.8 V or 55.6 V for lithium.
Tail current4% of capacityCharge current below which the battery counts as full.
Charged detection time3 minutesHow long both conditions must hold.
Peukert exponent1.25Corrects for lower capacity at high discharge rates. Use 1.25 for lead-acid if unknown, and 1.01 for lithium.
Charge efficiency factor95%Share of charge current that is actually stored.
Discharge floor50%Used for time-remaining and low-SOC alarms.

Synchronization

Small errors add up over days of cycling. The monitor corrects them by resetting to 100% each time the charged voltage and tail current conditions are met. If the charger's settings never satisfy these conditions, the reading drifts. Set the monitor's tail current higher than the charger's own tail-current threshold, so the monitor sees "full" before the charger stops.

Worked example: tracking state of charge

A 24 V, 280 Ah LiFePO4 bank is full at sunset. Overnight the house uses 1,800 Wh. At a nominal 25.6 V, that is 1,800 ÷ 25.6 = 70.3 Ah, so SOC falls to 100 − (70.3 ÷ 280 × 100) = about 75%.

The next morning the charge controller delivers 60 Ah before noon. With a 95% charge efficiency factor, the monitor counts 60 × 0.95 = 57 Ah as stored. SOC rises to 75 + (57 ÷ 280 × 100) = about 95%.

Once voltage reaches the charged setting and current falls below 4% of 280 Ah, which is 11.2 A, for 3 minutes, the monitor resets to 100%.

AC coupling

In an AC-coupled system, a grid-tie solar inverter is connected to the AC output of the off-grid inverter-charger instead of feeding a charge controller.

When the battery is full and the loads are small, the inverter-charger must slow the grid-tie inverter down. It does this by shifting its AC output frequency; the grid-tie inverter sees the frequency rise and reduces or stops its output. The equipment must be configured for this. Victron's Multis and Quattros do not shift frequency as shipped and need an assistant installed for off-grid AC coupling.

Victron sets out two rules for AC-coupled systems:

  • Factor 1.0 rule: the PV inverter's maximum power must be equal to or less than the inverter-charger's VA rating. A 3,000 VA unit supports up to 3,000 W of AC-coupled PV.
  • Minimum battery size: about 5 kWh of lead-acid battery per 1 kW of PV, or 4.8 kWh of lithium per 1.5 kW of PV.

Ignoring these limits can cause battery voltage spikes when the battery is nearly full, which can damage the inverter-charger, the PV inverter and connected loads. Victron also states that DC coupling through an MPPT controller is required for off-grid systems, because it lets the system recover after a shutdown, which AC coupling alone may not. For a new off-grid system, DC coupling is the simpler and more robust choice.

Day-to-day monitoring

Most current equipment reports through a display, a phone app or an internet portal. Remote monitoring suits a seasonal cabin left with a freezer or heat-trace running.

What to watch

  • Minimum daily SOC. The lowest point each morning shows whether the system is keeping up.
  • Whether the battery reached full. Lead-acid batteries need regular full charges. If absorption is rarely completed in winter, plan generator runs.
  • Daily solar yield. Compare similar sunny days. A sudden fall can mean snow cover, shading, a tripped breaker or a failed string.
  • Error and alarm history. Repeated overload, high-temperature or low-voltage events point to undersized cables, poor ventilation or loads beyond the system's capacity.

Alarms

Voltage sags under heavy load, so a voltage-only low-battery shutdown may trip during a pump start on a healthy battery. Where equipment allows it, base shutdown on the monitor's or BMS's state-of-charge reading. Set alarms for low SOC, high and low battery voltage, and high battery temperature. Choose a low-SOC alarm well above the inverter's shutdown point so there is time to start a generator or turn off loads. Where the inverter has a programmable relay, it can start a generator automatically on low SOC, provided the generator has an auto-start controller and is installed for unattended running.

Keep a log

Write down the main settings of every charger and monitor after commissioning, and again after any change. Monthly records of yield and minimum SOC show how the battery ages.

Key points

  • Set every charging source to the same voltages, taken from the battery maker, not factory defaults.
  • Size the inverter for its continuous rating at the warmest temperature it will see, and check both the surge figure and its duration.
  • Idle draw can cost 300 Wh or more a day. Use search mode where loads allow, or switch the inverter off when AC is not needed.
  • Set the inverter-charger's input current limit below the generator's rated continuous current.
  • Fit a battery temperature sensor for lead-acid compensation, and use the cold cut-off for lithium where the BMS does not handle it.
  • Route every negative connection through the shunt, and let the monitor synchronize at full charge regularly.
  • Use DC coupling for new off-grid systems. If you AC couple, follow the factor 1.0 rule and minimum battery size.
  • Get a permit and inspection where your province or state requires it.

This guide is general information. Codes, permits and safety requirements vary by province, state and municipality. Check local rules and use a qualified professional for electrical, gas, chimney and septic work where required.

The Comprehensive Off-Grid Manual

Every off-grid system in one manual, with worked examples, checklists and northern-climate detail.

Power

Off-Grid Batteries: LiFePO4 vs Lead-Acid

LiFePO4 vs lead-acid for off-grid power: usable capacity, cycle life, cold-weather charging, bank sizing, wiring, ventilation and lifetime cost.

13 min read
Power

The Electrical Load Audit and Efficiency

Measure every load with meters and battery monitors, find duty cycles and standby waste, plan peak demand, audit by season, and price efficiency upgrades.

13 min read