The wiring of an off-grid property carries more current, over longer distances, from more sources, than the wiring of most grid-connected homes. A battery bank can deliver enormous fault currents, low-voltage DC circuits lose power quickly over distance, and cables often run underground to pump houses, workshops and guest cabins. Correct conductor choice, overcurrent protection, burial and grounding are what keep that system from starting a fire or giving someone a shock. This guide covers the zones of an off-grid electrical system, conductor and cable types, the code rules for where overcurrent devices go and how large they may be, DC protection, low-voltage branch circuits, AC distribution with arc-fault and ground-fault protection, underground wiring, grounding electrodes, labelling and permits. Our solar power sizing guide covers the main battery fuse, PV conductor sizing and the single neutral-to-ground bond; this guide builds on those without repeating them.
The zones of an off-grid system
Think of the system as separate zones, each with its own voltage, current and protection needs.
| Zone | Typical voltage | Main hazards | Protection |
|---|---|---|---|
| PV array and source circuits | Up to the controller's input limit, often 100 to 250 V DC | DC arcs; voltage present in daylight | PV disconnect, string fuses where required |
| Battery and DC bus | 12, 24 or 48 V DC | Very high fault current | Main battery fuse, branch fuses or breakers, battery disconnect |
| DC branch circuits | 12, 24 or 48 V DC | Voltage drop, overheated small wire | Fuse or breaker for each circuit at the DC panel |
| AC output and distribution | 120/240 V AC | Shock, arcing faults, overloads | Breakers, AFCI and GFCI protection, distribution panel |
| Generator input | 120/240 V AC | Backfeed, neutral bonding errors | Inlet, transfer device or inverter-charger input breaker |
| Feeders to outbuildings | 120/240 V AC or DC | Voltage drop, buried cable damage, lightning | Feeder breaker, burial depth, surge protection |
Draw a one-line diagram of your system showing every source, every conductor with its size, and every fuse, breaker and disconnect. It is the best tool for finding unprotected conductors, and it shows an inspector the whole system at a glance.
Conductors and cable types
Copper and aluminum
Copper is standard for battery cables, inverter connections and most branch circuits. Aluminum is lighter and cheaper for long feeders, but needs a larger size for the same current and terminals rated for aluminum. The Canadian Electrical Code (CEC) rule on small conductors, described below, shows the difference: 10 AWG copper may be protected at up to 30 A, but 10 AWG aluminum only at 25 A.
Temperature ratings
Insulation is rated for a maximum conductor temperature, such as 60 °C, 75 °C or 90 °C. A conductor's ampacity depends on that rating, on the temperature rating of the terminals it connects to, on whether it runs in free air, conduit or a bundle, and on the surrounding temperature. Use the lowest rating in the circuit. A 90 °C cable connected to a breaker with 75 °C terminals must be sized at its 75 °C ampacity.
Cable for underground and outdoor runs
Ontario's Electrical Safety Authority lists examples of conductors, cables and raceways used for buried installations, including NMWU, USEI90, TECK90 and ACWU cables and PVC and DB2 raceway. Each cable type is approved for particular locations; check the marking on the jacket and the code tables before using it underground, in wet locations or in sunlight.
Battery and inverter cable
Use fine-stranded, flexible cable for battery and inverter connections, terminated with crimped lugs made for that cable. Support cables so the weight does not hang on terminals, protect them where they pass through enclosures, and keep positive and negative conductors together to reduce induced currents.
Where overcurrent protection goes
An overcurrent device, a fuse or breaker, protects the wire. Its job is to open the circuit before the conductor overheats. The CEC sets two basic rules.
Location: Rule 14-100
Overcurrent protection is required where a conductor receives its supply and at each point where the conductor size decreases. The rule allows limited exceptions, including:
- a smaller conductor already adequately protected by the upstream device;
- the "3 m rule": a smaller conductor up to 3 m long in armoured cable, metal-sheathed cable or non-ventilated raceway;
- the "one-third rule": a tap up to 7.5 m long whose ampacity is at least one-third of the conductor it is tapped from.
An off-grid system has supply at both ends of many conductors. A cable between a battery and a DC busbar can be fed by the battery in one direction and by a charge controller in the other, so a fault anywhere along it can draw current from the battery. That is why the battery end of every battery conductor is fused, and why each source connected to a busbar has its own protection.
Rating: Rule 14-104
The overcurrent device must not be rated higher than the allowable ampacity of the conductor. For small copper and aluminum conductors the CEC sets fixed maximums:
| Conductor | Maximum overcurrent device |
|---|---|
| 14 AWG copper | 15 A |
| 12 AWG copper | 20 A |
| 10 AWG copper | 30 A |
| 12 AWG aluminum | 15 A |
| 10 AWG aluminum | 25 A |
Exceptions cover cords and equipment wire, a code table that matches device ratings to conductor ampacities, and equipment such as motors, heaters and cooking units, which have their own rules. The same limits apply on DC circuits: a 12 V circuit wired in 14 AWG copper must not be fused above 15 A, however small the load.
DC protection
DC is harder to interrupt than AC. Alternating current passes through zero 120 times a second, which helps a breaker extinguish the arc; direct current does not. Every fuse and breaker in a DC circuit must therefore be rated for DC at the system voltage, and its DC interrupting rating must exceed the current the battery can deliver into a fault at that point.
- Use DC-rated devices. An AC-only breaker or a household plug fuse can fail to clear a DC fault and keep arcing.
- Check polarity. Some DC breakers are polarized and only interrupt correctly with current in the marked direction. Wire them exactly as labelled.
- Protect every branch at the DC panel. Each DC branch circuit, such as lighting, a refrigerator, a water pump or a radio, gets its own fuse or breaker sized to its conductor.
- Keep the battery end short. Mount the main battery fuse as close to the battery terminal as practical, so the length of unprotected cable is minimal.
- Use proper DC disconnects for the battery and PV array. Never open a loaded DC circuit by pulling a connector.
Low-voltage DC branch circuits
Running lights, a refrigerator or a water pump directly from the battery avoids inverter losses and idle draw. The cost is voltage drop: the same power at 12 V needs ten times the current of 120 V, and voltage drop is proportional to current.
Use the voltage drop method in our solar sizing guide. For small DC circuits, these copper resistances at 20 °C are useful: 14 AWG, 8.286 Ω/km; 12 AWG, 5.211 Ω/km; 10 AWG, 3.277 Ω/km.
Worked example: a 12 V refrigerator circuit
A 12 V refrigerator draws 5 A while running and sits 8 m (26 ft) of cable run from the DC panel. The manufacturer asks for no more than 3% voltage drop. Voltage drop = 2 × length × current × resistance.
- 14 AWG: 2 × 8 × 5 × 0.008286 = 0.66 V, which is 0.66 ÷ 12 = 5.5%. Too high.
- 12 AWG: 2 × 8 × 5 × 0.005211 = 0.42 V, which is 3.5%. Still too high.
- 10 AWG: 2 × 8 × 5 × 0.003277 = 0.26 V, which is 2.2%. Acceptable.
The circuit needs 10 AWG copper, which may be protected at up to 30 A under Rule 14-104. Fuse it to suit the refrigerator maker's recommendation, for example 10 A, which is well within the conductor's limit.
On a 24 V system the same refrigerator draws half the current, and the drop as a percentage of system voltage falls to a quarter: 12 AWG would give 1.7% and 14 AWG 2.8%.
Low voltage is also less forgiving of poor connections. A connection with a few hundredths of an ohm of resistance, insignificant at 120 V, can drop a significant share of 12 V and heat up. Use proper crimped terminals, tinned copper in damp locations, and check connections yearly.
AC distribution
The inverter's AC output should feed a distribution panel, not a single outlet or power bar. The conductor from the inverter to the panel needs overcurrent protection sized to the conductor and coordinated with the inverter's maximum output, usually with a breaker at the inverter or the panel as the inverter manual specifies.
Arc-fault and ground-fault protection
Under the 2021 Canadian Electrical Code, as summarized by Saskatchewan's Technical Safety Authority for homeowners:
- New receptacles in a dwelling unit require combination arc-fault circuit interrupter (AFCI) protection, including exterior receptacles on the dwelling.
- Exemptions include refrigerator and freezer receptacles on separate labelled circuits, kitchen island, counter and peninsula receptacles, bathroom basin receptacles, and single receptacles for a sump pump, septic pump or central heating equipment on a circuit serving nothing else.
- Ground-fault circuit interrupter (GFCI) protection is required for all exterior receptacles and for 15 A and 20 A receptacles within 1.5 m (59 in) of a sink.
- A 15 A circuit may serve no more than 12 general-purpose outlets, and a 20 A circuit no more than 16.
Requirements differ between code editions and provinces, and the US NEC has its own rules. Confirm the edition in force where you build.
Inverter compatibility
AFCI and GFCI devices work by sensing small differences in current or characteristic arcing signatures. If one trips without an apparent fault on an inverter-supplied system, check the inverter's neutral-to-ground bonding first, as described in our solar sizing guide, then ask the inverter and device manufacturers about compatibility.
Underground wiring
Buried cables to wells, outbuildings and arrays are where many rural installations fail inspection. The CEC's Rule 12-012 sets the requirements, summarized here from Ontario's Electrical Safety Authority and Technical Safety BC.
- Depth: minimum cover, measured from the top of the cable or raceway to finished grade, follows CEC Table 53. In areas subject to vehicles, Saskatchewan's Technical Safety Authority gives 900 mm (36 in) for direct-buried cable, and 600 mm (24 in) for cable in conduit, cable with a metal sheath or armour, or cable with mechanical protection.
- Mechanical protection: placing protection in the trench over the cable allows the minimum cover to be reduced by 150 mm (6 in). Accepted protection includes treated planking at least 38 mm (1.5 in) thick and poured concrete, concrete slabs or concrete encasement at least 50 mm (2 in) thick, extending at least 50 mm beyond the cables on each side. Creosoted wood is not recommended because it can damage cable insulation.
- Bedding: direct-buried cables run side by side without crossing, with at least 75 mm (3 in) of screened sand or screened earth of nominal 4.75 mm particle size above and below. No large rock, paving material, cinders or sharp or corrosive material in the trench.
- Marking: bury a marking tape about halfway between the cable and grade, or use permanent markers no more than 15 m (49 ft) apart and at every change in direction, with markers at each riser and building entry and a layout drawing at the panel.
- Bedrock: where rock prevents the required depth, armoured or metal-sheathed cable or raceways such as PVC or DB2 may run beneath grade-level concrete at least 100 mm (4 in) thick, with the location permanently marked.
- Frost and settlement: provide for movement with conduit expansion fittings or cable expansion loops, below grade and at terminations.
- Inspection: Technical Safety BC requires an inspection request before any underground installation is covered.
Worked example: a feeder to a workshop
A workshop 50 m (164 ft) from the panel needs a 240 V feeder for a 20 A load. Voltage drop for a two-wire 240 V circuit = 2 × length × current × resistance.
- 10 AWG copper: 2 × 50 × 20 × 0.003277 = 6.55 V, or 6.55 ÷ 240 = 2.7%.
- 8 AWG copper: 2 × 50 × 20 × 0.002061 = 4.12 V, or 1.7%.
If the circuit already loses 1 to 2% elsewhere, 8 AWG keeps the total near 3%. The cable must be a type approved for direct burial, laid on and covered with 75 mm of screened sand, at Table 53 depth, with marking tape halfway up the trench. Where it crosses the driveway, it must have 900 mm of cover if direct buried, or be in conduit or armoured cable at 600 mm.
Ask the inspector whether the workshop needs its own disconnecting means and grounding electrode under the code edition in force, and how they must connect to the bonding conductor that runs with the feeder.
Grounding electrodes and bonding
Bonding connects all exposed metal parts, such as enclosures, panel frames, racking and the inverter chassis, so that a fault cannot leave any of them at a dangerous voltage and so that fault current returns quickly enough to trip the overcurrent device. Grounding connects the system to the earth through a grounding electrode, which limits voltages from lightning and surges.
Canada
Section 10 of the CEC recognizes three kinds of grounding electrode: manufactured, field-assembled and in situ (Rule 10-102 in the 2018 edition). Requirements described in Alberta's 2018 code bulletin and in IAEI commentary include:
- Plate electrodes: buried at least 600 mm (24 in) below finished grade, meaning the expected final ground surface above the electrode. Under a basement, measure 600 mm below the final floor surface, not below the slab.
- Field-assembled electrodes: commentary on the 2006 code describes a bare copper conductor at least 6 m (20 ft) long, either in the bottom of a footing at least 600 mm below grade, or buried at least 600 mm below grade.
- In situ electrodes, such as a metal well casing or building steel, count only where enough of them lies in earth below 600 mm.
- Continuity: the grounding conductor must be electrically continuous throughout its length.
United States
Under the NEC, as summarized in Electrical Contractor magazine:
- rod and pipe electrodes must be at least 2.4 m (8 ft) long with at least that length in contact with soil;
- stainless or copper- or zinc-coated steel rods must be at least 16 mm (5/8 in) in diameter unless listed otherwise;
- a single rod, pipe or plate electrode must be supplemented by a second electrode at least 1.8 m (6 ft) away, unless the single electrode is shown to have a resistance to earth of 25 ohms or less;
- where bedrock is hit, a rod may be driven at an angle of no more than 45 degrees from vertical, or as a last resort laid in a trench at least 750 mm (30 in) deep.
Lightning and surges
Long overhead or buried runs to arrays, turbines and outbuildings collect surges from nearby lightning. Bond all metal structures to the grounding system, keep grounding conductors short and straight, and fit surge protection devices rated for the circuit's voltage at each end of long runs, as the equipment manufacturers recommend.
Labelling and documentation
- Label every breaker and fuse with the circuit it protects, in the panel directory.
- Label the battery disconnect, PV disconnect, inverter disconnect and generator input clearly, so anyone can shut the system down in an emergency.
- Post the one-line diagram near the main equipment, with conductor sizes and fuse ratings.
- Keep a layout drawing of all buried cables, with depths and measurements from fixed points.
Permits and inspection
All the work in this guide is electrical installation under the CEC as adopted by your province or territory, or the NEC as adopted by your state. Section 64 of the CEC covers renewable energy systems. Electrical permits and inspections are handled by the provincial or territorial authority, or by state and local authorities in the US. Some provinces allow homeowners to wire their own dwelling under a homeowner permit; others require a licensed electrician for some or all of the work. Saskatchewan's homeowner guidance, for example, directs owners to book a rough-in inspection with the local inspector before closing in the installation.
Key points
- Map the system into zones and draw a one-line diagram showing every source, conductor and protective device.
- Under CEC Rule 14-100, protect each conductor where it receives supply and where its size decreases; under Rule 14-104, never fuse above its ampacity (14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A).
- Use only DC-rated fuses and breakers on DC circuits, wired to their polarity markings, with interrupting ratings above the available fault current.
- Low-voltage DC circuits need large wire: a 5 A, 12 V load 8 m away needs 10 AWG to stay under 3% drop.
- Under the 2021 CEC, new dwelling receptacles need combination AFCI protection with listed exemptions, and GFCI protection outdoors and within 1.5 m of a sink.
- Bury cable to CEC Table 53 depths, in screened sand with marking tape, at 900 mm under driveways if direct buried, and get it inspected before backfilling.
- Bonding conductors clear faults; ground electrodes limit surges. Install both, and get the permit and inspection that apply where you live.
This guide is general information. Codes, permits and safety requirements vary by province, state and municipality. Check local rules and use a qualified professional for electrical, gas, chimney and septic work where required.
The Comprehensive Off-Grid Manual
Every off-grid system in one manual, with worked examples, checklists and northern-climate detail.
More guides
Off-Grid Solar Power: How to Size a System
Size an off-grid solar system for Canadian winters: load audit, peak sun hours, array, MPPT, inverter, wiring, fusing, with a full cabin example.
Off-Grid Batteries: LiFePO4 vs Lead-Acid
LiFePO4 vs lead-acid for off-grid power: usable capacity, cycle life, cold-weather charging, bank sizing, wiring, ventilation and lifetime cost.
The Electrical Load Audit and Efficiency
Measure every load with meters and battery monitors, find duty cycles and standby waste, plan peak demand, audit by season, and price efficiency upgrades.